Calculate / Heat Loss and Savings

Heat Loss and Savings

Calculators Heat leaving the surfaces in a year, its cost, and the gain over a bare steel envelope.

A significant part of the heat lost from a building in winter goes through the envelope. This calculation gives the heat leaving the panel-clad surfaces by conduction in a year and its money value, and sets beside it the loss those same surfaces would have if they were clad in uninsulated steel.

Distribution of the annual loss across the surfaces
Roof%5436,050 kWh
Wall%3020,367 kWh
Floor%1610,868 kWh

The percentages show which surface the heat lost in a year leaves through; together they add up to 100. Whichever surface carries the largest share, increasing the thickness there gains the most.

PIR
SurfaceWhere the panel sits on the building. CoreThe core of the panel. The thermal conductivity (λ) varies with the core. ThicknessThe insulation thickness, not the total thickness of the panel. AreaThe total panel area covered on this surface.
Roof
Wall
Floor
Roof, wall and floor are entered once each. + layer is for the case where a second panel is laid over an existing one: if PIR has gone over an old rock wool panel, there are two layers on the same area, their resistances add and the U-value falls.

This value is the annual heat loss through the building envelope by conduction alone; it does not represent the total energy consumption of the building. Ventilation, air leakage, windows, thermal bridges, internal gains and solar gains are not included.

Payback on the insulation investment Shows the payback on the total investment in the insulated panels selected, against the theoretical annual energy saving compared with the uninsulated steel reference. Enter the price per m² for each surface.
Panel investment
Theoretical annual energy saving
Payback period
Theoretical net gain over 10 years
Enter the panel price per m² for each surface to get the payback period. The results in this section are the output of a calculation. They are not an undertaking, a guarantee or a price quotation and cannot be used as such.
cold winter, -2 °C · Industrial building 2,700 m² of panel
67,286kWh/year For each surface, Q = U × A × DD × 24 / 1000. U is the thermal transmittance of the panel, A the area it covers and DD the heating degree days. The surfaces are added together.

Inside 18 °C, the temperature held in winter.

141,300 ₺ The annual loss is multiplied by the unit price entered. The price is the kWh price on your bill; change it and the figure changes. The annual cost of that heat, at 2,10 ₺/kWh.
3,589 A measure of the severity of the winter. The monthly average external temperatures in TS 825 Annex B.2 are taken; for every month below the internal temperature, (internal − external) is multiplied by the number of days in that month and the results are added. The larger it is, the greater the loss. Heating degree days
Against an uninsulated reference
With an uninsulated steel envelope3,024,978 ₺
With insulation141,300 ₺
2,883,678 ₺difference in annual heat loss The same surfaces are treated as clad in uninsulated trapezoidal sheet. The resistance of the steel itself is neglected, leaving the surface resistances: U = 1 / (Rsi + Rse), EN ISO 6946. 7.14 on a roof, 5.88 on a wall and 4.76 W/m²K on a floor. The difference between the two losses is the gain.

This value is the difference in annual conduction heat loss between an uninsulated steel envelope and the insulated envelope selected. It is not a saving on an actual energy bill.

By surface
Roof · PIR 60 mm 36,050 kWh · 54%
Wall · PIR 80 mm 20,367 kWh · 30%
Floor · PIR 100 mm 10,868 kWh · 16%
U-values
RoofU 0.35
recommended 0.25 · 90 mm brings it below the recommendation
WallU 0.26
recommended 0.35 · this selection is below the recommendation
FloorU 0.21
recommended 0.30 · this selection is below the recommendation
The smaller U is, the smaller the loss. The criterion is the TS 825 recommendation for heated buildings.
Method

The U-value is calculated to EN ISO 6946: R = Rsi + Σ(d/λ) + Rse, U = 1/R. The annual loss follows from the heating degree days, found for each month from the difference between the internal and external temperatures multiplied by the number of days. The monthly average external temperatures are taken from TS 825:2024 Annex B.2 and the internal temperatures from Annex B.1.

Scope

The result is the heat leaving the panel-clad surfaces by conduction. Windows, doors, floor slabs, ventilation, thermal bridges and internal gains are not included; all of those belong to the energy calculation for the building and cannot be done without looking at the project.

Criterion

The recommended values on the card come from TS 825:2024 Annex A.2 and are shown as a single line for the climate and surface selected; the whole table is not published. Those values are for heated buildings and are on an element basis: what binds is the annual heating energy calculation for the building, and a suitable result can be reached for the building as a whole while one element is above the recommendation. This table is not required for unheated warehouses, canopies, partitions and cladding. Outside Türkiye the limits vary by country; each country sets them in its own regulations, and in that case you can enter your own target.

Get a quote

Tell us about your project and our sales team will come back within 24 hours.

Product groups *
Approximate m²